Description

Main
Range of product EOCR
Device short name EOCR-3DM2

EOCR 3DM2-WRDUWZ

Product or component type Protection relay
Protection type Overload, In > OC setting
Underload, In < UC setting
Locked rotor for starting, In > 2…8 times OC setting
Locked rotor for running, In > 1.5…5 times OC setting
Sensitivity to phase loss
Phase unbalance, 10…50 %
Sensitivity to phase reverse
Product specific application Motor protection
Network type AC
Network frequency 50…60 Hz
protection ajustment range 0.5…60 A
Tripping threshold 0.5…32 A (inverse and thermal)
0.5…60 A (definite)
Complementary
[Us] rated supply voltage 100…240 V AC/DC
Mounting support 35 mm DIN rail
Panel
Contacts type and composition 1 NC + 1 NO (OL)
1 NO (AL/UL/TO)
Short-circuit and overload protection By 4 A gG fuse
[Ue] rated operational voltage 600 V AC 50…60 Hz for power circuit conforming to UL
690 V AC 50…60 Hz for power circuit conforming to CSA
690 V AC 50…60 Hz for power circuit conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-4-1
Reset Manual reset
Automatic reset 0.5…1200 s
Electrical 0…1 s by interruption of power supply
Time delay type D-Time: 0…200 s
O-Time: 0.2…30 s (definite)
O-Time: 1…30 class (inverse and thermal)
U-Time: 0.5…30 s
Display type Bar graph
7 segments LED
power consumption per relay 3 W
Connections – terminals Control circuit: cable 2 x 1…1.5 mm²flexible with cable end – M3
Control circuit: cable 2 x 1…1.5 mm²flexible without cable end – M3
Control circuit: cable 1 x 1…2.5 mm²flexible with cable end – M3
Control circuit: cable 1 x 1…2.5 mm²flexible without cable end – M3
Tightening torque Control circuit: 0.8…1.2 N.m on cable, 4.7 mm
Height 74.5 mm
width 70 mm
Depth 83.8 mm
Net weight 0.315 kg
Environment
Standards IEC 60947-4-1
Product certifications UL
IP degree of protection IP20 conforming to IEC 60529
Ambient air temperature for operation -20…60 °C conforming to IEC 60947-4-1
Ambient air temperature for storage -40…85 °C
Operating altitude 2000 m
Fire resistance 650 °C conforming to IEC 60695-2-12
960 °C conforming to UL 94
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-7
Vibration resistance 4 gn on panel mounting conforming to IEC 60068-2-6
2 gn on 35 mm DIN rail conforming to IEC 60068-2-6
Dielectric strength 2 kV 50…60 Hz in between case and circuit conforming to IEC 60255-5
1 kV 50…60 Hz in between contact conforming to IEC 60255-5
2 kV 50…60 Hz in between circuit conforming to IEC 60255-5
Surge withstand 6 kV conforming to IEC 61000-4-5
Electromagnetic compatibility Resistance to radiated electromagnetic fields: 10 V/m level 3 conforming to IEC 61000-4-3
Resistance to electrostatic discharge: 8 kV air, 6 kV contact conforming to IEC 61000-4-2
Resistance to fast transient: 2 kV conforming to IEC 61000-4-4
Conducted RF disturbances: 10 V conforming to EN 61000-4-6
Conducted RF disturbances: class A conforming to EN 55011
[Ith] conventional free air thermal current 3 A for control circuit
Permissible current 250 V, 3 A AC
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 10.2 cm
Package 1 Width 9.3 cm
Package 1 Length 8.3 cm
Package 1 Weight 325.0 g
 
Warranty 18 months